Hidden Failure Detection Prevents 197 MWh of Energy Loss in PV Inverter
Delfos platform identified a critical inverter failure missed by SCADA, preventing 197 MWh in energy loss. Discover how predictive analytics delivered real operational value.
Using Delfos' advanced analytics, the engineering team uncovered a failure not detected by SCADA, preventing over 197 MWh in energy losses.
Context
During routine monitoring of a solar plant, Delfos' platform detected a significant anomaly: inverter INV14 was showing a much lower specific production (kWh/kWp) compared to other inverters with the same nominal capacity (see Figure 1).
Figure 1. Specific production of the inverter before maintenance.
This discrepancy hinted at hidden generation losses was not reported by the plant’s SCADA system.
Implemented Solution
The low specific production of inverter INV14 served as the starting point for the investigation by the performance engineering team. With the support of Delfos' analytics platform, the team conducted a deeper analysis using two critical tools:
Lost Energy Ranking: which revealed the energy losses at the string level.
Deviation Analysis: which highlighted abnormal behavior in the normalized DC power of specific strings.
This investigation led to the identification of 8 inoperative strings, all linked to DC Switch 2, which had been disconnected. Furthermore, the switch presented a communication failure, preventing any alarms from being raised in SCADA.
The anomaly was reported during a regular Engineering & Performance meeting, prompting the client's O&M team to inspect the asset and reconnect the switch, restoring the inverter’s performance.
Results
After maintenance, the inverter’s performance returned to expected levels, matching the specific production of other equivalent inverters (see Figure 2).
Figure 2. Specific production of the inverter after maintenance.
Estimated energy loss avoided: 197.42 MWh (over ~6 months)
Root cause identified despite no SCADA alarm
Corrective action executed promptly based on Delfos insights
Want to know if hidden losses are affecting your plant? Request a free loss analysis or book a live demo with our team.
Conclusion
Delfos enabled the identification of a critical failure that went undetected by traditional monitoring systems, showcasing the power of intelligent, string-level analysis. By providing actionable insights, Delfos empowered the client to restore inverter performance, avoid further losses, and improve overall plant reliability.
Insights
197.42 MWh of recovered energy
0 SCADA alarms triggered during the failure
8 disconnected strings identified
Over 40% drop in specific production during the issue (from ~22 to ~12.9 kWh/kWp)
FAQ
What is an “invisible” SCADA failure in a solar inverter?
In many solar PV plants, SCADA alarms only react to communication errors or critical trips, so hidden performance losses can run for months without any alert. This “invisible” SCADA failure is an electrical or operational issue that reduces production but does not trigger traditional alarm thresholds.
Delfos solves this industry problem by continuously comparing the specific production (kWh/kWp) of each inverter and string against similar assets. In this case, the platform highlighted one inverter with much lower specific production than inverters of the same nominal power, flagging a hidden failure that SCADA alone could not see.
How did Delfos recover 197 MWh of hidden energy losses?
The plant was unknowingly losing energy because one inverter was operating with significantly reduced specific production over several months. Without advanced analytics, this kind of loss is typically only discovered after a physical inspection or a revenue gap.
Delfos used its predictive analytics platform to detect the anomaly early and quantify the lost energy. By pinpointing the faulty inverter and the affected strings, the O&M team corrected the issue and avoided an estimated 197.42 MWh of additional lost production over a six-month period, directly protecting revenue.
Why did the plant’s SCADA system show zero alarms during the fault?
Traditional SCADA systems are not designed to capture every type of performance degradation. In this case, the CC2 breaker was disconnected and had a communication failure, so the associated strings were not producing energy but no SCADA alarm was generated. From a control-room perspective, everything appeared normal.
Delfos bridges this monitoring blind spot by using performance-based alerts instead of relying only on SCADA tags. The platform detected that the inverter’s specific production had dropped by more than 40% (from about 22 kWh/kWp to ~12.9 kWh/kWp) and highlighted the issue to the O&M team, even though SCADA reported zero alarms.
Which Delfos tools were used to detect the faulty strings?
In large PV plants, O&M teams struggle to see which strings are driving losses across thousands of data points. Manually checking each string in SCADA is time-consuming and often reactive.
Delfos solved this by combining two key tools in its platform:
1. Lost Energy Ranking
This feature ranked the non-generated energy by string, showing exactly where the largest losses were concentrated inside the inverter.
2. Deviation Analysis
The deviation tool compared the normalized DC power of each string against expected behavior, clearly exposing eight inoperative strings. Together, these analyses led the Engineering team directly to the disconnected CC2 breaker as the root cause.
What operational results were achieved after Delfos flagged the issue?
When hidden failures persist, solar plants suffer from lower yield, underestimated performance risk, and unnecessary site inspections. Fixing problems late often means permanent revenue loss.
After Delfos reported the anomaly in the regular Engineering & Performance meeting, the O&M team acted quickly and corrected the breaker and string issue. The inverter returned to the expected specific production pattern, again aligned with equivalent inverters. As a result:
• An estimated 197.42 MWh of future energy losses were avoided over six months.
• Eight disconnected strings were restored to normal operation.
• No preliminary field inspection was needed before taking the corrective action.
How does Delfos improve day-to-day O&M decision-making?
O&M teams often lack a clear, data-driven view of where to act first, especially when SCADA dashboards show “no alarm” but production is underperforming. This leads to low-priority tickets, reactive work, and missed revenue.
Delfos turns plant data into actionable insights by ranking lost energy by asset, comparing inverter and string behavior, and highlighting deviations that matter for revenue. In this case, Delfos translated abstract SCADA and field data into a concrete, high-impact maintenance action, enabling precise and fast intervention instead of broad, exploratory inspections.
What were the key performance indicators in this solar inverter case?
Many plants track only basic KPIs, which can mask serious underlying issues. Without deeper analytics, metrics like “availability” and “alarms count” are often misleading for revenue protection.
Delfos focused on KPIs directly linked to value in this case:
• Energy recovered: 197.42 MWh of energy losses avoided (six-month estimate).
• Root cause: eight disconnected strings due to the CC2 breaker issue and communication failure.
• SCADA behavior: 0 alarms registered during the entire failure period.
• Performance deviation: more than 40% drop in specific production, from ~22 kWh/kWp to ~12.9 kWh/kWp.
By tracking these KPIs, Delfos directly links technical anomalies to financial impact, helping asset owners and O&M teams prioritize what truly moves the P&L.
How does Delfos compare to traditional SCADA monitoring in PV plants?
Relying only on SCADA for fault detection exposes solar portfolios to invisible losses and delayed interventions. SCADA is essential for control and safety, but it is not designed to quantify lost energy or benchmark asset performance.
Delfos complements SCADA with AI-driven performance analytics and clear lost-energy insights, as highlighted below:
Industry Challenge
Traditional SCADA Monitoring
Delfos Predictive Analytics Platform
Detect hidden performance losses
No alarm when communication fails or when losses are below fixed thresholds; invisible faults can persist for months.
Identifies abnormal specific production and DC power deviation at inverter and string level, even with zero SCADA alarms.
Quantify lost energy per asset
Limited or no native view of non-generated energy by string or inverter.
Lost Energy Ranking shows how much energy each string or inverter is failing to generate, in MWh.
Prioritize O&M actions
O&M teams work reactively and often need field inspections to confirm suspected issues.
Directs teams to the exact component (e.g., breaker and strings) responsible for the loss, enabling fast, targeted interventions.
Protect revenue and plant KPIs
Energy losses are only visible after production or revenue deviations become material.
Prevents long-lasting hidden losses (197.42 MWh in this case), improving yield, reliability, and financial performance.
When should asset owners and O&M teams use Delfos for inverter performance issues?
Solar operators often notice underperformance late, either in monthly reports or when contractual KPIs are already at risk. Waiting for manual analysis or generic reports to reveal issues can lock in permanent revenue loss.
Delfos is most valuable when you want continuous, proactive surveillance of inverter and string behavior. The platform automatically monitors specific production, lost energy, and deviations across the fleet, and then surfaces anomalies in regular Engineering & Performance reviews. This gives O&M teams the time and clarity they need to correct failures before they escalate into major financial losses.
How does Delfos turn predictive analysis into measurable financial value?
AI and analytics only create value when they change operational decisions and protect cash flow. Many tools stop at dashboards, leaving O&M teams unsure how to act on the information.
Delfos connects predictive insights with concrete O&M actions. In this case, the platform not only detected the anomaly but also indicated the affected inverter, strings, and likely electrical cause. This enabled a precise, low-cost corrective action that avoided 197.42 MWh of future energy losses, increased operational reliability, and generated direct financial returns for the asset owner.
See how many hidden SCADA failures Delfos can uncover in your solar portfolio.